EDITORIAL CALENDAR 2000 Browse By... Technology/Topic Vendor Back Issues Content LAB TEST CENTER TECH TUTORIALS GLOBAL NETWORKS N.P.N. PRODUCT LEADERS OPINIONS/COLUMN Viewpoint INDUSTRY PIPE Visitor's Center FAQs Contact the Editors Free Newsletter Subscriptions Marketing Services Industry Front & Center Reader Service Custom Publishing Real World Seminars Vendor Strategies CommWeb Sites Computer Telephony Call Center Teleconnect ISPs Tele.com
|
|
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
||||||
| Cable insulation | Performance rating/ top data rate | Plenum approved | Cost per 1,000 feet | Characteristics | By-products when burned | Toxicity rating (LC50)* |
| Halogen FEP (fluorinated ethylene propylene) | Category 5/100 Mbit/s | Yes | $275 | Low smoke, high toxicity; highly fire resistant | Hydrogen fluoride, carbon monoxide | LC50 range = 36.1 to 77.1 |
| Halogen PVC (polyvinyl chloride) | Category 3/10 Mbit/s | No | $100 | High smoke, high toxicity; low fire resistance | Hydrogen chloride, dioxin, carbon monoxide | LC50 range = 10 to 20.6 |
| Halogen-free (various metal hydrates) | Category 5/100 Mbit/s | No | $160 | Low smoke, low toxicity; fire resistant until metal hydrate exhausted | Steam, carbon monoxide | LC50 range = 4.4 to 15.6 |
| * Toxicity is measured using the LC50 rating, which indicates the number of grams of insulation that must be burned to kill half the mice in a lab experiment. LC50 ratings supplied by the State of New Yorkís Hazardous Materials Bureau. | ||||||
When FEP cable burns it releases hydrogen fluoride, an odorless invisible gas that is considerably more toxic than hydrogen chloride. Tests conducted at University of Pittsburgh in the 1980s also indicate the presence of another, far more deadly gas, in FEP fumes--known in the cable industry as "the supertoxin." Some scientists theorize the gas is a fluoro-phosgene--the fluorine equivalent to the phosgene gas used in World War I. The supertoxin was never properly identified, and resear ch into it has now ceased. "We know there's hydrogen fluoride, but that's not the real problem," says BGH's Hirschler. "There's something else in the gases, and nobody knows what it really is except that it's highly, highly toxic."
Not all researchers agree with Hirschler's assessment. "Most people have largely put the supertoxin down as a laboratory phenomenon, not a real-world phenomenon," says Edward Weil, professor at Polytechnic University (Brooklyn, N.Y.), which conducts research into halogen and halogen-free cabling.
FEP's poisonous potential has prompted some grisly jokes at cabling companies. "The advantage of fluorine cable is that the firemen can see your body and step over it when they arrive to put out the fire," says Paul Chalifour, senior manager of market development at Nordx/CDT, a subsidiary of Cable Design Technologies Corp. (Pittsburgh). Like almost all cable companies, Nordx sells halogen and halogen-free cabling.
Champions of halogen-fr ee cable are quick to point out that in a fire what can't be seen is far more lethal than what can. Invisible gases given off by burning material are the cause of more than 80 percent of fire deaths, according to research published in the British Medical Journal . In the U.S. that translates into as many as 6,000 deaths a year. And halogen's opponents are sure that the chemicals are killers.
Most of the available data on cable toxicity was gathered after the State of New York changed its building code in 1988, requiring that all cabling products be tested for toxicity--the only state ever to do so. The tests were conducted by Anderson Laboratories (West Hertford, Vt.) on behalf of the National Electrical Manufacturers Association (NEMA, Rosslyn, Va.).
Anderson Labs measured cable toxicity on mice in a laboratory using the so-called Pittsburgh Test (named for the university where it was developed). In the test, a specific amount of insulation is burned, with the fumes shunted throug h a tube to four mice. This procedure is repeated with more insulation until two of the mice are dead. The insulation is then assigned an LC50 (life count 50) toxicity rating that indicates the number of grams of insulation that had to be burned to kill half the test animals. The higher the LC50 rating, the less toxic the cable. Over 1,000 tests were conducted.
Data Communications obtained the LC50 ratings from the State of New York's Hazardous Materials Bureau (see Figure 1). They show that halogen FEP cable is more than 5 times as toxic as halogen-free and 1.5 times as toxic as halogen PVC.
Exposing laboratory mice to the fumes produced by burning
insulation makes it possible to measure cable toxicity. The LC50
rating indicates how many grams of insulation had to be burned to kill
two of the four mice in each round of tests. The lo
wer the rating,
the more deadly the fumes. The results show that FEP cable is more
than 5 times as toxic as its halogen-free counterpart and roughly 1.5
times as deadly as PVC cabling.
|
The NFPA, the nonprofit association that oversees the national code, doesn't dispute FEP's lethal nature. "If the plenum tests were based only on toxicity, Teflon FEP is probably the only material that would not pass," says Arthur Cote, vice president and chief engineer. "It's an order of magnitude higher in terms of toxic potency than almost any other material in use today."
But Cote, who also is secretary of the NFPA's toxicity advisory committee, doesn't think the code should be changed, citing doubts about the Pittsburgh Test methodology.
Other halogen advocates also challenge the test results . Some argue that the findings are academic because the tests don't mirror real-world conditions. "By the time the levels of heat in a building were high enough to release those gases, everyone would be dead anyway," says Al Scolnik, vice president of power distribution products at NEMA and former director of NEMA's wire and cable division.
Halogen defenders also argue that autopsies of fire victims usually show carbon monoxide poisoning as the cause of death--not hydrogen chloride or hydrogen fluroide. And they add that cables only contribute a small amount of smoke to a fire. Computer simulations by the National Research Counsel of Canada suggest that less than 12 percent of the smoke comes from cable.
The anti-halogen forces have answers ready on all counts. For one thing, they argue that while carbon monoxide poisoning may be the direct cause of death in a fire, acid gases can disorient victims and prevent them from escaping a burning building. What's more, they assert that where cable is located is just as important as the smoke it gives off. Since building plenum is typically used by the air-conditioning system, wiring ducts can distribute toxic fumes throughout the workplace--even if a fire hot enough to release the fumes is restricted to a small area. "If there's smoke in the plenum return it can be sucked back and redistributed," explains Mike Kerwin, principal at Cablenet System Inc. (Woburn, Mass.), which installs cabling systems for corporations and educational organizations.
That appears to be what happened during a fire at Düsseldorf Airport in Germany last April in which 16 people were killed and more than 60 hospitalized for smoke inhalation.
The fire appears to have been sparked off by welders working in a combined ventilation and cable shaft in the main arrival hall. According to the British newspaper The Independent , "PVC-covered cables began to smolder, emitting cyanide, chloride, carbon monoxide, and poss ibly dioxin fumes that spread through the building's ventilation shafts." The International Herald Tribune reported that the "fire carried a flood of lethal fumes into elevators, ventilation ducts, and passenger lounges."
That sort of disaster makes halogen opponents understandably nervous--especially since there's far more cable in building plenums than ever before. "There wasn't much wire above ceilings 10 years ago. Since then, the amount of cabling has gone up by several orders of magnitude," says Richard Bukowski, senior research engineer at the building and fire research laboratory of the National Institute of Standards and Technology (NIST, Gaithersburg, Md.). "The bigger the fuel load, the bigger the concern over fumes," he adds.
"There should be controls on where you can use halogen cable. The last place you want it is in a plenum. If you must run it there it's essential that it's contained in a rigid conduit or pipe," says McCormack of the International Association of Fi refighters. He notes that conduit is compulsory in only two U.S. cities: Chicago and New York.
Critics of halogen cable also argue that cable manufacturers and chemical companies have a vested interest in maintaining the status quo. FEP cabling is about 40 percent more expensive than halogen-free. DuPont has even more to lose; it has an almost total lock on the FEP market, accounting for over 90 percent of production.
Some observers claim that the big cable and chemical manufacturers have used undue influence to prevent code changes. "The only reason we can't spec halogen-free is because of political maneuvering by the cabling companies," says Allen Kasiewicz, president of Trellis Communications Corp. (Manchester, N.H.), a cabling installer and consultancy.
But evidence backing up those charges is virtually nonexistent. And it's worth noting that the NFPA limits the number of panelists from any one organization to prevent packing the committees that discuss c ode changes. Of course, there are loopholes. As well as its official delegates, DuPont staffers attend NFPA meetings under the guise of the Chemical Manufacturers Association. Still, its representatives only make up a fraction of the 400 people that are involved in the review process.
As indicated, zero-halogen advocates are gearing up for a new campaign aimed at amending the next edition of the national code. But rather than once again taking the toxic tack, the latest push focuses on the catastrophic damage that smoke can cause to computer and networking equipment. "It's the next big battle," says Tom Ebert, engineering group leader at Underwriter's Labs Inc. (Elkhart, Ind.), which is developing a new corrosivity test.
Both sides agree that there's a problem. "There are numerous examples of multimillion dollar damages after even a very small PVC fire," says Poul Villien, coordinating manager at 3P Third Party Testing (Hoersholm, Denmark), an independent test facility.
"Even a smoldering fire can wreak havoc on a modern office. It doesn't have to be big enough to set off the sprinklers," agrees Tom Chapin, member of the technical staff at Lucent Technologies (the recent AT&T consolidation, Murray Hill, N.J.), which sells both halogen and halogen-free cabling.
Despite the apparent agreement, it's by no means certain that the latest bid to permit the use of halogen-free cable in plenum airspace will be any more successful than earlier efforts. Once again, it's up to the advocates of change to prove that halogen-free cables are safer--although this time the debate centers on hardware rather than human beings. And the pro-halogen group is already preparing its counteroffensive.
What may make the anti-halogen push even harder is that there's less consensus on gauging corrosivity than there is on measuring toxicity. Currently, there are about 20 different tests used worldwide.
In Europe, cable corrosivity is gener ally matched to the PH value of the gas that's emitted when the insulation burns. (Levels of 1 to 4 are deemed corrosive, levels of 5 and above are not.) When PVC burns it produces hydrogen chloride, which has a PH level of 1. When FEP insulation burns it releases hydrogen fluoride, which has a PH level of 3 to 4. When halogen-free cables burns it gives off steam, which has a PH level of 6.5 to 8.5.
But some observers believe PH values are only part of the story. "Smoke particles can have a traumatic effect on closely spaced electronic components on a circuit board. And the PH test doesn't measure the highly conductive ionic contaminants that can be produced when cable burns," says Chapin.
Lucent has come up with a new test--called an interdigitated comb pattern--that it claims more accurately emulates the effects of fire on a PC board. The test bed comprises two interleaved copper combs. Smoke is passed across the combs, and the amount of electrical leakage is then measured.
Chapin sa ys test results show that going with zero-halogen cable doesn't guarantee fewer problems. "Some of the halogen-free cables are great. But some of them approach the corrosivity of halogen cabling." Given that finding, Chapin recommends that net managers wait for cross-comparison testing of cables to be performed and the findings published before opting for any particular brand. But with so many different tests in use, net managers still have the problem of whose results to trust.
In the end, it may take more than testing, lobbying, or even common sense to force a change in the U.S. codes. "There's an on-off attitude about fire safety," says Rosalind Anderson, president of Anderson Laboratories. "If you haven't killed anyone important recently, then it's not an issue."